Method 1: Adding A Hole
Common Uses:
Attics, kneewalls, smaller cavities (bays, floor systems)
Measurements:
1) With house at 50 Pa, measure zone pressure differences-house-
to-zone, zone-to-exterior, and house-to-exterior-checking that the
first two add up to the third.
2) Add a hole to inside surface, for example open the attic or
kneewall access fully or partly.
3) Remeasure pressures-making sure house is depressurized 50
Pa, adjusting fan as needed.
- If pressures change little (less than 10 Pa), make the hole larger.
- If house-to-zone pressure difference is near zero, make hole
smaller.
4) Pressure drop (Step 3) = decrease in house-to-zone pressure
from added hole.
5) Measure size of hole in square inches.
Calculations
6) In the Method 1
graph, find initial house-to-zone pressure difference on
horizontal axis.
7) Find where this value intersects the "Pressure drop" curve
corresponding to the value in Step 4.
8) On left axis, find the "Leakage rate between house and zone per
square inch added hole (cfm50/in2)."
9) The house-to-zone leakage rate = value in Step 8 x the area of
hole.
10) Calculate zone-to-exterior and total path leakages by looking
up multipliers from
Table 1. (Look in the column
labeled with the initial house-to-zone pressure difference.) Then
multiply each value by house-to-zone leakage rate (Step 9).
Method 1 works best when the initial pressures are not near 0 Pa or
50 Pa and the pressure drop is substantial (for example, 15-25
Pa).
Table 1. Method 1 Multipliers
Initial pressure difference, house-to-zone (Pascals) 10 15 20 25 30 35 40 45 48 49
Multiplier to obtain zone-to-exterior leakage rates(1) 0.4 0.6 0.8 1.0 1.3 1.7 2.5 4.2 7.9 12.6
Multiplier to obtain total flow path leakage rates(2) .35 .46 .55 .64 .72 .79 .87 .93 .97 .99
(1) Ratio of zone-to-exterior leakage rate to house-to-zone leakage rate
(2) Ratio of total flow path leakage rate to house-to-zone leakage rate