Home Energy Magazine Online March/April 1998
Efficient Cooling: Making It Happen
by Craig Sherman and Eric Hildebrandt
What's the best way to size a residential
air conditioner? To what extent do air conditioners tend to be oversized?
How can energy research and programs help promote optimal sizing of cooling
systems? These questions can heat up a discussion, but a new study suggests
solutions that help everyone.
 |
 |
| Figure 1. This graph shows current sizing
practice (black bars) and the sizing that would have resulted if contractors
all used a common rule of thumb (grey bars). Assuming that Manual J
is ideal, current practice is to oversize air conditioners in Sacramento,
and the rule of thumb would have resulted in slightly more oversizing.
Still, the rule of thumb is close enough to Manual J that Sacramento
homeowners can use it as a check against more extreme oversizing. |
 |
| SMUD Energy Services inspected 40 homes where new air conditioners
and heat pumps were installed. Here, Craig Sherman calculates room-by-room
cooling loads using the RHVAC software package from Elite Software. Like
Right-J from Wrightsoft, RHVAC is based on Manual J by the Air Conditioning
Contractors of America. |
 |
| Utilities can encourage proper equipment sizing through direct contractor
referrals, lists of approved contractors, and informational tips. Bill
stuffers and "bangtails" like this one advertise these information services
to all customers, and encourage those who want new HVAC equipment to request
detailed information. This envelope went out with SMUD bills in the summer
of 1996, with a cover reading, "Are you greeted by a BLAST of hot air?" |
| Table 1. Potential Savings from
Reducing Size of Installed Equipment Based on Manual J Load Calculations |
| Average Added Equipment Cost from Oversizing |
Extra Cost/Ton* |
Added Cost of .65 Tons/Unit |
Added Cost of .30 Tons/Unit |
| Wholesale prices |
| Small (2-3-ton units) |
$404 |
$263 |
$121 |
| Medium (3-4-ton units) |
$539 |
$350 |
$162 |
| Large (4-5-ton units) |
$674 |
$438 |
$202 |
| Installed cost: high-volume sales |
| Small (2-3-ton units) |
$792 |
$515 |
$238 |
| Medium (3-4-ton units) |
$844 |
$549 |
$253 |
| Large (4-5-ton units) |
$1,042 |
$677 |
$313 |
| Installed cost: low-volume sales |
| Small (2-3-ton units) |
$937 |
$609 |
$281 |
| Medium (3-4-ton units) |
$989 |
$643 |
$297 |
| Large (4-5-ton units) |
$1,187 |
$772 |
$356 |
| * Based on installed costs for high efficiency residential
air conditioners (12 SEER) in the 1994 Measure Cost Study, prepared for
California Demand-Side Management Measurement Advisory Committee (CADMAC)
by XENERGY Incorporated, November 1994. |
|
As part of its efforts to promote energy-efficient
residential HVAC systems, the Sacramento Municipal Utility District (SMUD)
looked into air conditioner sizing. SMUD found that the problem of oversized
air conditioners may be much less serious than previous studies have suggested,
but that most home air conditioners are still sized larger than Manual
J recommends (see "Bigger Is Not Better: Sizing
Air Conditioners Properly," HE May/June '95, p. 19). Results of this
research suggest a variety of ways in which utilities and other energy
education programs may
effectively promote more efficient sizing of residential cooling equipment.
SMUD's research suggests that installing smaller
HVAC equipment may save real money for contractors and homeowners alike.
These first-cost savings alone may pay for the extra cost of "rightsizing"
HVAC equipment. Between comfort, efficiency, and first-cost savings, there
are a variety of selling points that can be used to promote proper sizing
of HVAC equipment. While most utility programs have focused on training
HVAC contractors, These selling points could also increase customer demand
for rightsized cooling equipment.
What's the Debate?
When it comes to how air conditioners should be
sized, there's a wide gap between the perspectives of residential energy
researchers and HVAC installers. Most researchers agree that central air
conditioners are frequently oversized--at least from the standpoint of
overall operating efficiency. They say that air conditioners run most efficiently
when they are allowed to operate for extended periods, rather than frequently
cycling on and off. On a hot day, a larger air conditioner that has just
been turned on can bring the house to the thermostat setpoint several minutes
faster than a smaller unit. But under more typical conditions, the larger
unit will usually operate much less efficiently, and won't usually provide
better comfort (see "If Bigger Is Not Better,
What Is?" HE Sept/Oct '96, p. 13).
To ensure proper sizing of air conditioners,
these efficiency-minded experts recommend that contractors use Manual
J, a methodology developed jointly by the Air Conditioning Contractors
of America (ACCA) and the Air-Conditioning and Refrigeration Institute
(ARI). Manual J is a building load calculation method based on complex
modeling and analysis. It makes fewer simplifying assumptions than most
other load calculation methods that contractors use. Still, some experts,
such as John Proctor of Proctor Engineering in San Rafael, California,
believe that Manual J results may actually size equipment larger
than efficiency and comfort require, particularly in dry climates. In fact,
Proctor has found evidence that Manual J may overestimate building
cooling loads by as much as 50%.
Rather than using Manual J to determine
the cooling load, most contractors use simpler, less time-consuming methods
that err further toward oversizing. These methods provide wider margins
of safety against equipment undersizing--at the expense of efficiency.
Virtually every equipment contractor has a story to show why bigger is
usually better for ensuring adequate cooling on the hottest days of the
year, avoiding complaints, and satisfying customers.
Most contractors are not aware that Manual
J already incorporates a margin of safety. And, its margin may not
be large enough to accommodate poorly designed or malfunctioning air handling
systems, leaky ducts, and inadequately charged refrigerant.
Some contractors believe that sizing units larger
provides a margin of safety that can compensate for such problems and prevent
customer complaints or callbacks. However, even significant oversizing
of the air conditioning unit is unlikely to mask more serious problems
in the air distribution system.
Methods for Sizing Air Conditioners
Contractors and engineers use many different methods
to determine the cooling load. Methods range from Manual J calculations
to simple rules of thumb. Some contractors have even developed customized
spreadsheets based on building size and types. When an air conditioner
rebate program at Pacific Gas and Electric Company (PG&E) asked contractors
for their load calculation methodologies, the utility received over 40
different calculations. One common rule of thumb in the Sacramento area
is to allow 1 ton of sensible cooling capacity for every 500 ft2
of conditioned space, or about 1 ton of total capacity per 650 ft2.
Contractors who do not use Manual J typically
spend about 30 minutes assessing the type and size of equipment to install
on a residential installation. They claim that including a detailed room-by-room
Manual
J calculation increases the time to about four hours--two hours to
collect data on-site and two hours to enter the data into a software program
and analyze the results.
For a typical home in the Sacramento area, contractors
charge at least $200 for a Manual J load calculation. The cost can
be significantly higher for large or unusual homes. On the other hand,
in new construction, mechanical system sizing can be included in the energy
code compliance calculations.
Some researchers don't think it takes that long
to complete Manual J. According to Proctor, "it takes much less
time and skill to do a whole-house Manual J than a room-by-room
assessment, and for the purpose of sizing the air conditioner, a whole-house
calculation is adequate. It takes about 30 minutes to gather the data in
the home and enter it at the same time."
Research in Sacramento
To determine the extent of oversizing in the SMUD
service area, we selected a sample of 40 homes that had received a new
cooling unit in 1995 under SMUD's rebate, financing, and quality assurance
program. During 1995, nearly three-fourths of customers replacing central
cooling equipment in Sacramento participated in SMUD's program.
The sample used in this study included equipment
installed by 22 different contractors. Together, these 22 contractors account
for about two-thirds of the air conditioners and heat pumps installed through
the program. The largest 5 of these contractors alone accounted for over
half of all equipment installed with SMUD rebates or financing.
We looked at all system types installed through
the program. The percentage of each type used in the study was proportional
to the percentage of that type installed through the program. We inspected
each home used in the study, collecting enough data to perform room-by-room
Manual
J load calculations using the RHVAC program by Elite Software.
We used these load calculations to estimate the
sensible cooling load in each home. Calculations were performed using Manual
J recommended design temperatures for Sacramento's climate. We then
compared the sensible load estimate from Manual J to the sensible
capacity of the installed equipment from manufacturers' specifications.
For the sake of comparison, we also compared the size of the installed
equipment to what would have been installed using the rule of thumb of
1 ton of sensible cooling capacity per 500 ft2. Finally, we
researched the incremental costs of different sizes of cooling equipment
and calculated the potential equipment cost savings from rightsizing equipment
based on Manual J.
Less Oversized Than Expected
We found that equipment tended to be oversized relative
to Manual J load calculations (see Figure 1).
One-third of the 40 cooling units inspected were sized within .25 ton of
Manual
J, while 53% of the units were oversized by at least .25 ton. Only
15% of the sample were oversized by .75 ton or more. Overall, equipment
was oversized by an average of .30 ton.
However, the percentage of units oversized by
1 ton or more was significantly lower than that reported in several other
recent studies. We found only 10% to exceed Manual J calculations
by 1 ton or more. A previous study in the Pacific Northwest placed this
figure at 33%; another, in PG&E service territory in California, placed
it at 53%.
Only about 13% of the sample was undersized by
more than .25 ton, and only two of these were units undersized by more
than 20%--the level of oversizing that seems to be built into Manual
J (see "How Big Is Enough,"
HE Sept/Oct '96, p. 17).
How Good Are Simple Rules of Thumb?
Rules of thumb are often thought to lead to equipment
oversizing. However, results of SMUD's research indicate that using a simple
rule of thumb (1 ton of sensible cooling capacity for each 500 ft2
of conditioned space) would result in only slightly more oversizing than
methods used to size equipment in the 40 homes in the study. Fifty-three
percent of the units in the study were found to be oversized by at least
.25 ton compared to Manual J; 60% would have been that oversized
if this simple rule of thumb had been used to size all 40 units. On average,
units would have been oversized by .35 ton using this rule of thumb, compared
to the average oversizing of .30 ton in the sample.
Sizing equipment with Manual J would result
in significant savings to customers and contractors by reducing equipment
and operating costs. Table 1 shows the estimated range
of potential first-cost savings that could be achieved by installing the
generally smaller equipment called for by Manual J calculations.
Since the cost of installed equipment depends on the size of equipment
and type of vendor (wholesale, high-volume contractor, low-volume contractor),
savings were calculated based on a range of costs for different equipment
and sales types.
For the 53% of customers in the study sample
who could have downsized equipment by following Manual J, average
first-cost savings would range from $515 to $770, based on an average reduction
of .65 ton per unit. If all units had been sized with Manual J, eliminating
both undersizing and oversizing, average first costs would still drop between
$240 and $350 per installation.
The potential savings from downsizing cooling
equipment appear to compare favorably with the additional labor cost of
performing more detailed load calculations. Manual J calculations
can be worthwhile, since on average, savings from reduced equipment costs
are likely to at least equal the $200 to $250 that local contractors charge
for a Manual J calculation. If local contractors were to follow
Proctor's advice and do the simpler whole-house load calculation, the savings
would be even more dramatic.
In addition to savings from reduced equipment
costs, using Manual J to size air conditioners reduces energy costs
by increasing operating efficiency. Proctor estimates that a unit oversized
by 1 ton may operate up to 7% less efficiently than a unit sized based
on Manual J. For a typical home in Sacramento, which may use 1,200
kWh per year for cooling, this represents additional savings of about $8
per year, or a discounted present value of $65 over a 15-year life of the
equipment.
Working with HVAC Contractors
In the past, most efforts to promote proper sizing
of cooling equipment have been focused on HVAC contractors working with
customers through utility rebate or financing programs. But even utilities
that do not offer rebates or financing for HVAC equipment can encourage
proper equipment sizing by providing customers with direct contractor referrals
and lists of approved contractors. Utilities and other organizations may
use a variety of approaches to work with contractors to promote better
equipment sizing.
One innovative utility program was PG&E's
1994 air conditioning rebate program. To qualify for the program, contractors
were required to submit the methodologies they used to perform load calculations.
Methods were approved if the utility found they yielded building load calculations
within 20% of Manual J. Contractors were then required to submit
actual load calculations, using the approved methodology, for each installation.
Another option for utilities is to require load
calculations only when the size of newly installed equipment varies from
the size of previously installed equipment, and for installations in homes
that did not previously have central cooling. However, it can be difficult,
costly, or impossible for utilities to actually verify the size of previously
installed equipment.
Another variation on this approach would be to
offer an incentive to contractors to get them to submit the methodologies
they use and some specific samples to the utility. The utility could then
compare these results to load calculations based on Manual J and
find ways to improve the methodologies to result in better equipment sizing.
Perhaps the ideal option would be to develop
more simplified sizing methodologies that compare favorably with Manual
J for the local climate--but require less time to perform. Contractors
participating in energy efficiency programs could be either required or
encouraged to utilize this type of simplified calculation. Most of the
time required to perform a Manual J calculation is spent collecting
room-by-room information and entering the data into a computer. A computer
can perform the actual Manual J calculations in seconds. Simplified
methods may reduce data collection and inputs; hopefully, this would not
come at the expense of precise load calculations.
Creating Customer Demand for Proper Sizing
Utilities and other organizations promoting energy
efficiency don't have to work only with contractors. They can employ a
variety of approaches for creating increased customer demand for properly
sized HVAC equipment (see "Homeowners: Who Will Demand Rightsizing?").
Relatively little seems to have been done to pursue this customer-driven
approach; utility programs and other informational efforts have been focused
almost exclusively on HVAC contractors. Programs can offer rebates, financing,
contractor referrals, or information to customers. The agency sponsoring
the program can then provide targeted information and recommendations to
customers early in the decision-making process.
Most importantly, perhaps, customers should be
made aware of the tendency for cooling systems to be oversized, and the
fact that oversized equipment costs more to purchase as well as to operate.
For instance, local customers should know that about half the new systems
in our study were oversized, and that on average an oversized system costs
at least $515 more than a unit sized according to Manual J. These
kinds of numbers might pique homeowners' interest in rightsized equipment.
Homeowners can be encouraged to question sizing
recommendations. They can ask contractors the size of proposed new equipment
and the size of existing equipment. When a homeowner who is satisfied with
an existing system is offered larger equipment, he or she should be prepared
to ask for a more detailed explanation. In such cases, homeowners can also
ask contractors to provide cost estimates for both sizes of equipment in
order to quantify the higher first cost of oversizing.
To estimate the approximate size of the unit
they need, homeowners in the Sacramento area can use the rule of thumb
of 1 ton of sensible cooling capacity for every 500 ft2 of conditioned
space in their home. This method would let a homeowner know if the unit
is grossly over- or undersized. It might be possible to develop rules of
thumb with similar levels of reliability for other climates. If the contractor
proposes installing a unit that is larger than the local rule of thumb
would indicate, the homeowner should ask him or her to explain why. The
homeowner can also ask the contractor to provide cost estimates for both
sizes of equipment.
Homeowners can also ask contractors to explain
and document of the method used to determine what size equipment to install.
Although it may be difficult or impossible for most homeowners to assess
the accuracy of different sizing methods, asking for this information may
help differentiate between the contractors who follow very simple rules
of thumb and those who do more detailed sizing calculations.
In addition, since contractors frequently offer
customers more than one sizing option, efficiency programs can advise customers
about the potential tradeoff between overall efficiency and rapid cooling.
Homeowners can also be educated about alternatives to oversizing, such
as programmable thermostats and dual-speed air conditioners.
Craig Sherman and Eric Hildebrandt are with
Energy Services' Research and Evaluation Section at the Sacramento Municipal
Utility District in Sacramento, California.